Compakt Solo NBR - closed
Available in 7 days, delivery time 1-3 working days
Ideal sealing of wall penetrations for gas, water, sewage pipes, and cables. |
Material type | NBR-Rubber |
Bolts | V2A stainless steel |
Shore hardness | Shore A 40° ±5 |
Pressure plates | V2A stainless steel |
Rubber thickness | 40 mm |
UV-resistant | No |
Temperature range | -30 °C to + 120 °C |
Pressure-tight | 3 bar |
Description | pressure-tight up to 3.0 bar, with an ejection safety device up to 5.0 bar |
|
Core drill hole | 80 mm |
---|---|
Medium pipe | 20-28 mm |
Features
Special applications for different pipe systems Consist of stainless steel pressure plate All Compakt Solo split versions are foldableAreas of application
Sealing for wall penetrations of gas, water, sewage pipes and cables Against pressing and non-pressing waterDescription
The rubber element is compressed by means of two metal discs.
The Compakt seals the annular space between carrier pipe and casing pipe/core hole against water and gas.
Assembly Instructions
1 | Clean casing pipe/core drilling and carrier pipe. Carrier pipes must be suitable, dimensionally stable and without damage in the sealing area. Core drillings have to be made true to scale and with a smooth inner side. |
2 | We recommend coating core drillings with ProteX epoxy resin in order to protect the concrete and smoothen possible cavities/grooves. |
3 | Verify the casing pipe/core drilling and carrier pipe diameters based on the sealing kit data. Insert the Compakt seal into the casing pipe or core drilling flush with the wall and insert the carrier pipe. Care must be taken to ensure the sealing insert is mounted on the outside of the building (tolerance for the carrier pipes). |
! | If pipelines are already installed, the hinged version (Fig. 1) can be folded out, placed around the pipeline and securely locked with the lock. The split version with puzzle lock (Fig. 2) must be dismantled and mounted on the pipe before installation. Subsequent division of the rubber element (Fig. 3) must be carried out with a sharp cutter knife at an angle to the holes. Thus, the existing pipes and cables can be inserted into the sealing rubber, fix the pressure plates back on the rubber element and finish the installation. |
What needs to be taken into account?
- The Compakt seal is not an anchorpoint or pipe support. The seal can only assume a sealing function
- The carrier pipes have to be centred and supported (fixed)
- We recommend reducing the respective maximum torques in case of particularly thin-walled plastic pipes such as flexible casing and corrugated pipes (see table below)
- For long clamping strokes, deep hexagon sockets are additionally required for installation
- All building and pipeline guidelines are to be observed
- Use only in suitable casings acc. table Installation tolerances with suitable sealing surface in the inner wall and suitable rigidity (dimensional stability after installation)
Note on installation
We expressly draw your attention to the fact that the installation must be carried out by an authorized specialist company in accordance with the installation instructions.
Tools
Cleaning material/preparation, measuring tool, torque wrench, aids for markings
Recommendation
To create a suitable sealing surface, we recommend coating core holes with PSI KB epoxy resin. This serves to protect the concrete and to smooth out any blowholes/grooves
|
|
|
|
|
|
PSI Products GmbH
Ulrichstrasse 25
72116 Mössingen
Telefon: 0 049 (0)7473 37 81 0
E-Mail: vertrieb@psi-products.de